Hey I need your help.

Recently I bought a Riello NPW 2000 that output a “pseudo-sinusoidal” wave when running on battery the fact is that I read on the web that modern servers could have problems with it.
Mostly right, as I found that my server (poweredge t430) is not running good with it. When unplugging the power to test the UPS sometimes it make the server just power off and reboot (as said in the bios, turn on when power goes on again) or it put the ups in safety mode (continuous beep).
Tried disabling the PFC in IDRAC settings, as far I haven’t noticed power off issues but only safety mode issues with the UPS… (So in fact the server power off, but will never go on battery)

In both cases the server is running fine on battery the issues are just happening when switching.

If anyone has an idea… Thank you

After research I found that the server never turns off when disabling PFC but will eventually make the UPS goes into fault, I fought it was the fault of the PC that was putting the UPS in protection mode, but it was not the case as I tried to power a TV and it did the same thing… So I’m good to buy another one…

EDIT : some clarifications & partly resolving the issues

  • 667
    link
    fedilink
    English
    arrow-up
    4
    ·
    6 days ago

    There are some devices which will protest under modified sine wave, and some which may even get damaged. I recently accepted the risk of using an msw inverter with some electronics and did not notice any issues, but I had read that the device would be fine with it.

    • cmnybo@discuss.tchncs.de
      link
      fedilink
      English
      arrow-up
      2
      ·
      5 days ago

      Computer power supplies won’t be damaged by modified sine wave inverters. Be sure to test your power supply on the UPS when nothing important is running though. Some power supplies will shut down as soon as the UPS switches to battery.

      • 667
        link
        fedilink
        English
        arrow-up
        3
        ·
        5 days ago

        That’s my thought, that the power blip is basically too long, and why I suggest to OP to try a different UPS.

    • foremanguy@lemmy.mlOP
      link
      fedilink
      English
      arrow-up
      2
      ·
      6 days ago

      Seen that dell server PSUs are not really friendly with mdw but when PFC disabled it should not pose problems… But here it does

      • 667
        link
        fedilink
        English
        arrow-up
        1
        ·
        6 days ago

        Well, might have to do some isolation tests if you can borrow a pure sine wave UPS and see if it makes a difference. Outside of that, the power blip might be too much for the power supply to handle or it trips up BIOS/mobo voltage sampling.

        • foremanguy@lemmy.mlOP
          link
          fedilink
          English
          arrow-up
          1
          ·
          6 days ago

          Sadly I don’t have a pure sine wave UPS, but if I’d tried it I would replace my riello one. But I think that it would work with the server… Do you think it’s any good to try to find a solution or buy a rsw one?

          • 667
            link
            fedilink
            English
            arrow-up
            2
            ·
            6 days ago

            Ideally you’d isolate the UPS as the problem, so it would be good if you could borrow one for a few days or so to check. It could be that the UPS isn’t the problem.

            Consider reviewing the return policy of a company where you can get a pure sine wave inverter and if it fixes the problem you’re good, and you’ve already got your replacement. Else, there may be a configuration or hardware problem.